Category  Error Code  Description  How to fix them 
Size  parameters. 
H’1201012D 
Consumed TAG does not 
exist. 
Check if the parameters in the Consumed tag are 
set correctly.   
H’1201012E 
Produced TAG does not 
exist. 
Check if the parameters in the Produced tag are 
set correctly. 
H’12010204 
Unconnected request timeout 
No response from the adapter; check if the power 
and the network connection for the adapter are 
working properly.   
H’12010302 
Network bandwidth NOT 
available for data 
1.  Check the I/O connection limit between the 
scanner and the adapter. 
2.  Increase the RPI value or reduce the number of 
connections.   
H’12010315 
Invalid segment in 
connection path 
Check the module number and the product setup 
file to see if they match.   
 
9.6.2.2 Application Error
 
Category  Error Code  Description  How to fix them 
EtherNet/ 
IP Error 
H’00010203  I/O connection timeout   
1.  Check the network connection status. 
2.  Check if the module is working properly. 
3.  Increase the RPI value.