Chapter 6 Control TerminalsC2000 Plus
6-8
6-2 Control Terminal Specifications
MI1
+
24 V COM FWD
MO1
MI5MI3
ACI+1 0V AVI
A F M1 MO 2
MCM
MI 7
MI4DC M RE V MI 2 MI 8MI6ACM-10V AU IAFM2
DFM
SG-SG+
RA2RC2RB2 RB1RC1 RA1
0-10V
-10 -10V
0-10V 0-10V
0-10V
0-20mA
0-2 0m A
0 -20mA Open
120
AFM 1
AFM2
AVI
A CI 485
SGN D
STO 1 S TO 2
SCM1SCM2DCM
+24V
B
A
C
Figure 6-14. Removable Terminal Block
Function
name
Area Conductor
Stripping
Length
(mm)
Maximum
Wire Gauge
Minimum
Wire Gauge
Tightening
Torque
(±10 %)
RELAY
Terminals
Conductor cross
section solid wire
4–5
1.5 mm²
(16 AWG)
0.2 mm²
(26 AWG)
5 kg-cm
(4.3 lb-in.)
(0.49 Nm)
Conductor cross
section stranded wire
Control
Terminals
Conductor cross
section solid wire
6–7
8 kg-cm
(6.9 lb-in.)
(0.78 Nm)
Conductor cross
section stranded wire
Control
Terminals
Conductor cross
section solid wire
2 kg-cm
(1.7 lb-in.)
(0.20 Nm)
Conductor cross
section stranded wire
Table 6-1
Wiring precautions:
In the figure above, the factory default for STO1, STO2, +24V and SCM1, SCM2, DCM are
short-circuited. Use the +24V power supply of the safety function (as shown in section of
above figure) for STO only. Do NOT use it for other purposes. The factory setting for +24V-COM
is short-circuited and SINK mode (NPN); please refer to Chapter 4 Wiring for detail.
Tighten the wiring with slotted screwdriver:
Ⓐ Ⓑ is 3.5 mm (wide) x 0.6 mm (thick); is 2.5 mm (wide) x 0.4 mm (thick)
When wiring bare wires, ensure that they are perfectly arranged to go through the wiring holes.
Terminals Terminal Function Factory Setting (NPN mode)
+24V
Digital control signal common
(Source)
+24V 5% 200 mA
COM Digital control signal common (Sink) Common for multi-function input terminals
FWD
Forward-Stop command
FWD-DCM:
ON
forward running
OFF
deceleration to stop
REV Reverse-Stop command
REV-DCM:
ON
reverse running
OFF
deceleration to stop

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
AltitudeUp to 1000m without derating
CommunicationCANopen
Output Current2.5A
Protection FeaturesOvercurrent, Overvoltage, Overtemperature
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Humidity95% RH (non-condensing)