Chapter 7 Optional AccessoriesC2000 Plus
7-9
7-2 Magnetic Contactor / Air Circuit Breaker and Non-fuse Circuit Breaker
Magnetic Contactor (MC) and Air Circuit Breaker (ACB)
It is recommended the surrounding temperature for MC should be 60°C and that for ACB should be
50°C. In the meanwhile, consider temperature derating for components with ON/OFF switch in accordance
with the ambient temperature of the on-site distribution panel.
230V models
Frame Model
Heavy Duty
Output Current (A)
Heavy Duty
Input Current (A)
MC/ACB
Selection (A)
A
VFD007C23A-21 5 6.4 11
VFD015C23A-21 8 12 22
VFD022C23A-21 11 16 32
VFD037C23A-21 17 20 32
B
VFD055C23A-21 25 28 55
VFD075C23A-21 33 36 65
VFD110C23A-21 49 52 85
C
VFD150C23A-21 65 72 130
VFD185C23A-21 75 83 150
VFD220C23A-21 90 99 150
D
VFD300C23A-00
VFD300C23A-21
120 124 185
VFD370C23A-00
VFD370C23A-21
146 143 225
E
VFD450C23A-00
VFD450C23A-21
180 171 265
VFD550C23A-00
VFD550C23A-21
215 206 330
VFD750C23A-00
VFD750C23A-21
255 245 400
F
VFD900C23A-00
VFD900C23A-21
346 331 500
460V models
Frame Model
Heavy Duty
Output Current (A)
Heavy Duty
Input Current (A)
MC/ACB
Selection (A)
A
VFD007C43A-21
3 4.3 7
VFD015C43A-21
4 5.9 9
VFD022C43A-21
6 8.7 18
VFD037C43A-21
9 14 22
VFD040C43A-21
10.5 15.5 32
VFD055C43A-21
12 17 32
B
VFD075C43A-21
18 20 32
VFD110C43A-21
24 26 40
VFD150C43A-21
32 35 55
Table 7-7

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
BrandDelta
ModelC2000 Plus Series
CategoryDC Drives
LanguageEnglish

Related product manuals