Chapter 7 Optional AccessoriesC2000 Plus
7-38
DC Reactor
A DC reactor can also increase line impedance, improve the power factor, reduce input current,
increase system power, and reduce interference generated from the motor drive. A DC reactor stabilizes
the DC bus voltage. Compared with an AC input reactor, a DC reactor is in smaller size, lower price, and
lower voltage drop (lower power dissipation).
Installation
Install a DC reactor between terminals +2/DC+ and +1/DC+. Remove the jumper, as shown in the
figure below, before installing a DC reactor.
Figure 7-23 Wiring of DC reactor
Applicable Reactors
200V–230V, 50/60 Hz
Model HP
Heavy Duty Super Heavy Duty
Rated
current
(Arms)
Saturation
current
(Arms)
DC reactor
(mH)
DC reactor
Delta Part #
Rated
current
(Arms)
Saturation
current
(Arms)
DC reactor
(mH)
DC reactor
Delta Part #
VFD007C23A-21
1 5 9 8.64 DR005D0585 3 6 9.762 N/A
VFD015C23A-21
2 8 14.4 12.78 DR008D0366 5 10 5.857 DR005D0585
VFD022C23A-21
3 11 19.8 18 DR011D0266 8 16 3.66 DR008D0366
VFD037C23A-21
5 17 30.6 28.8 DR017D0172 11 22 2.662 DR011D0266
VFD055C23A-21
7.5 25 45
43.2 DR025D0117 17 34 1.722 DR017D0172
VFD075C23A-21
10 33 59.4
55.8 DR033DP851 25 50 1.172 DR025D0117
VFD110C23A-21
15 49 88.2 84.6 DR049DP574 33 66 0.851 DR033DP851
VFD150C23A-21
20 65 117
111.6 DR065DP432 49 98 0.574 DR049DP574
VFD185C23A-21
25 75 135
127.8 DR075DP391 65 130 0.432 DR065DP432
VFD220C23A-21
30 90 162 154.8 DR090DP325 75 150 0.391 DR075DP391
Table7-41