Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-01-12
the loaded regenerative energy to steadily and smoothly stop the motor in the fastest deceleration
time.
4 (stall prevention by auto-acceleration and deceleration–reference to the acceleration and
deceleration time settings): if the acceleration and deceleration time are within a reasonable range,
the actual acceleration and deceleration time refer to Pr.01-12–01-19 settings. If the acceleration
and deceleration time are too short, the actual acceleration and deceleration time are greater than
the acceleration and deceleration time settings.
01-45
Time Unit for Acceleration / Deceleration and S-Curve
Default: 0
Settings 0: Unit: 0.01 sec.
1: Unit: 0.1 sec.
01-46
CANopen Quick Stop Time
Default: 1.00
Settings Pr.01-45 = 0: 0.00–600.00 sec.
Pr.01-45 = 1: 0.0–6000.0 sec.
Sets the time required to decelerate from the maximum operation frequency (Pr.01-00) to 0.00
Hz through the CANopen control.
01-49
Deceleration Method Selection
Default: 0
Settings
0: Normal deceleration
1: Over-voltage energy restriction
2: Traction energy control (TEC)
3: Electromagnetic energy traction control

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
AltitudeUp to 1000m without derating
CommunicationCANopen
Output Current2.5A
Protection FeaturesOvercurrent, Overvoltage, Overtemperature
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Humidity95% RH (non-condensing)

Related product manuals