Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-01-16
01-54
Zero-Speed Delay Time Out
Default: 0.00
Settings 0.00–655.35 sec.
If the actual (or estimated) rotor frequency fails to be restrained under the Pr.01-53 frequency
level, and the difference error is not triggered, the drive may be unable to stop outputting. Set
this parameter for this condition. When the frequency command decelerates to the minimum
frequency and starts to count, this function forces the drive to stop outputting when it reaches
the Pr.01-54 setting time.
The actual motor speed reaches the Pr.01-53 level in Pr.01-54 setting time, and the drive stops
outputting when the counting reaches Pr.01-52 setting time (Pr.01-54 setting time is still
counting):
The motor actual speed does not reach the Pr.01-53 level in Pr.01-54 setting time: