Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-02-6
Settings Functions Descriptions
13
Cancel the setting of
auto-acceleration / auto-
deceleration time
Set Pr.01-44 to one of the 01–04 setting modes before using this
function. When this function is enabled, OFF is for auto mode and
ON is for linear acceleration / deceleration.
14
Switch between motor 1
and motor 2
ON: use parameters for motor 2
OFF: use parameters for motor 1
15
Rotating speed
command form AVI
ON: force the source of the drive’s frequency to be AVI. If the
rotating speed commands are set to AVI, ACI and AUI at the same
time, the priority is AVI > ACI > AUI.
16
Rotating speed
command form ACI
ON: force the source of the drive’s frequency to be ACI. If the
rotating speed commands are set to AVI, ACI and AVI at the same
time, the priority is AVI > ACI.> AUI
17
Rotating speed
command form AUI
ON: force the source of the drive’s frequency to be AUI. If the
rotating speed commands are set to AVI, ACI and AVI at the same
time, the priority is AVI > ACI.> AUI
18
Forced to Stop
(Pr.07-20)
ON: the drive ramps to stop according to the Pr.07-20 setting.
19 Frequency up command
ON: the frequency of the drive increases or decreases by one
unit. If this function remains ON continuously, the frequency
increases or decreases according to Pr.02-09 / Pr.02-10.
If the frequency command has to retern to zero when the AC
motor drive stops, then you should set Pr.11-00 bit7 = 1.
20
Frequency down
command
21
PID function disabled ON: the PID function is disabled.
22 Clear the counter
ON: the current counter value is cleared and displays 0. The
drive counts up when this function is disabled.
23
Input the counter value
(MI6)
On: the counter value increases by one. Use the function with
Pr.02-19.
24
FWD JOG command
This function is valid when the source of the operation command
is external terminal. ON: the drive executes forward JOG. When
executing the JOG command in torque mode, the drive
automatically switches to speed mode. The drive returns to torque
mode after the JOG command is complete.
25 REV JOG command
This function is valid when the source of the operation command
is external terminal. ON: the drive executes reverse JOG. When
executing the JOG command in torque mode, the drive
automatically switches to speed mode. The drive returns to torque
mode after the JOG command is complete.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
AltitudeUp to 1000m without derating
CommunicationCANopen
Output Current2.5A
Protection FeaturesOvercurrent, Overvoltage, Overtemperature
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Humidity95% RH (non-condensing)