Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-06-4
Abnormal condition: DC bus > Pr.06-01 Over-voltage stall prevention
1. Pr.06-02 = 0:
During deceleration, the drive maintains the DC bus voltage and slowly decrease the output
frequency (which takes a long time to decelerate to 0 Hz).
2. Pr.06-02 = 1:
If you set Pr.06-01 to a small value that lower than the DC bus voltage, the drive maintains
the DC bus voltage and the output frequency during deceleration. To prevent this situation,
modify the Pr.06-01 setting to a value larger than the DC bus voltage (Pr.06-01 is able to be
set during operation).
Related parameters:
Pr.01-13, Pr.01-15, Pr.01-17, Pr.01-19 Deceleration Time 1–4
Pr.02-13–Pr.02-14 Multiple-function Output (Relay 1 and Relay 2)
Pr.02-16–Pr.02-17 Multiple-function Output (MO1 and MO2)
Pr.06-01 Over-voltage Stall Prevention.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
AltitudeUp to 1000m without derating
CommunicationCANopen
Output Current2.5A
Protection FeaturesOvercurrent, Overvoltage, Overtemperature
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Humidity95% RH (non-condensing)

Related product manuals