EasyManua.ls Logo

Delta C2000 Plus Series - Page 591

Delta C2000 Plus Series
1259 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-06-4
Abnormal condition: DC bus > Pr.06-01 Over-voltage stall prevention
1. Pr.06-02 = 0:
During deceleration, the drive maintains the DC bus voltage and slowly decrease the output
frequency (which takes a long time to decelerate to 0 Hz).
2. Pr.06-02 = 1:
If you set Pr.06-01 to a small value that lower than the DC bus voltage, the drive maintains
the DC bus voltage and the output frequency during deceleration. To prevent this situation,
modify the Pr.06-01 setting to a value larger than the DC bus voltage (Pr.06-01 is able to be
set during operation).
Related parameters:
Pr.01-13, Pr.01-15, Pr.01-17, Pr.01-19 Deceleration Time 1–4
Pr.02-13–Pr.02-14 Multiple-function Output (Relay 1 and Relay 2)
Pr.02-16–Pr.02-17 Multiple-function Output (MO1 and MO2)
Pr.06-01 Over-voltage Stall Prevention.

Table of Contents

Related product manuals