Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-06-24
06-49
Lvx Auto-Reset
Default: 0
Settings 0: Disabled
1: Enabled
06-50
Time for Input Phase Loss Detection
Default: 0.2
Settings 0.00–600.00 sec.
06-51
Capacitance oH Warning Level (Applied to 230V / 460V Models)
Default: Depending on the
model power
Settings 0.0–110.0 degree
Set the over-heat warning level of the drive’s internal DC bus capacitor.
When the setting is less than 10.0 degree, the drive uses its internal capacitor oH warning level.
06-52
Ripple of Input Phase Loss
Default:
Settings 230V models: 0.0–160.0 V
DC
30.0
460V models: 0.0–320.0 V
DC
60.0
575V models: 0.0–400.0 V
DC
75.0
690V models: 0.0–480.0 V
DC
90.0
06-53
Input Phase Loss Detection Action (OrP)
Default: 0
Settings 0: Fault and ramp to stop
1: Fault and coast to stop
When the drive detects the DC bus ripple exceeds the setting for Pr.06-52, and lasts for the time
of Pr.06-50 plus 30 seconds, the drive executes the input phase loss protection according to Pr.06-
53.
During the time of Pr.06-50 plus 30 seconds, if the DC bus ripple drops lower than the setting for
Pr.06-52, the Orp protection recalculates.
06-55
Derating Protection
Default: 0
Settings 0: Auto-decrease carrier frequency and limit output current
1: Constant carrier frequency and limit output current
2: Auto-decrease carrier frequency
Refer to Pr.00-01 (Maximum Operation Frequency) for allowable maximum output frequency in
each control mode.
The corresponded carrier frequency lower limit under each control mode:
VF, SVC, VFPG, and PM Sensorless:
Maximum operation frequency (Pr.01-00) × 10
minimum sampling point limit.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
AltitudeUp to 1000m without derating
CommunicationCANopen
Output Current2.5A
Protection FeaturesOvercurrent, Overvoltage, Overtemperature
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Humidity95% RH (non-condensing)

Related product manuals