Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-08-8
Serial Connection
Parallel Connection
08-08
Feedback Signal Detection Time
Default: 0.0
Settings 0.0–3600.0 sec.
Valid only when the feedback signal is ACI (4–20 mA).
This parameter sets the detection time for abnormal PID signal feedback. You can also use it
when the system feedback signal response is extremely slow. (Setting the detection time to 0.0
disables the detection function.)