Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-14-4
14-18
Extension Card Input Selection (AI10)
Default: 0
Settings 0: 0–10 V (AVI10)
1: 0–20 mA (ACI10)
2: 4–20 mA (ACI10)
14-19
Extension Card Input Selection (AI11)
Default: 0
Settings 0: 0–10 V (AVI11)
1: 0–20 mA (ACI11)
2: 4–20 mA (ACI11)
When you change the input mode, verify that the external terminal switch (AI10, AI11) is in correct
position.
14-20
AO10 DC Output Setting Level
14-21
AO11 DC Output Setting Level
Default: 0.00
Settings 0.00–100.00%
14-22
AO10 Filter Output Time
14-23
AO11 Filter Output Time
Default: 0.01
Settings 0.00–20.00 sec.
14-36
AO10 Output Selection
14-37
AO11 Output Selection
Default: 0
Settings 0: 0–10 V
1: 0–20 mA
2: 4–20 mA