Chapter 13 Warning CodesC2000 Plus
13-14
ID No. Display on LCD Keypad Warning Name Description
11
PID feedback error
(PID)
PID feedback loss (warning for analog feedback signal;
works only when PID enables)
Action and Reset
Action condition When the analog input is lower than 4mA (only detects analog input of 420mA)
Action time Pr.08-08
Warning setting parameter
Pr.08-09
0: Warn and keep operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: Warn and operate at last frequency
Reset method
Auto
Warningoccurs when Pr.08-09=0 or 3. The Warning
automatically
clears when the feedback signal is larger than 4mA.
Manual Error” occurs when Pr.08-09=1 or 2. You must reset manually.
Reset condition Immediately reset
Record
Records when Pr.08-09=1 or 2 (“Error”).
Does not record when Pr.08-09=3 (“Warning”).
Cause Corrective Actions
Loose or broken PID feedback
wiring
Tighten the terminals again.
Replace with a new cable.
Feedback device malfunction Replace with a new feedback device.
Hardware error
If the PID error still occurs after checking all the wiring,
return to the factory for
repair.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
BrandDelta
ModelC2000 Plus Series
CategoryDC Drives
LanguageEnglish

Related product manuals