Chapter 13 Warning CodesC2000 Plus
13-16
ID No. Display on LCD Keypad Warning Name Description
13
Under current
(uC)
Low current
Action and Reset
Action condition Pr.06-71
Action time Pr.06-72
Warning setting parameter
Pr.06-73
0: No function
1: Fault and coast to stop
2: Fault and ramp to stop by 2
nd
deceleration time
3: Warn and operation continue
Reset method
Auto
Warningoccurs when Pr.06-73=3. The Warningautomatically clears
when the output current is > (Pr.06-71+0.1A).
Manual Error” occurs when Pr.06-73=1 and 2. You must reset manually.
Reset condition Immediately reset
Record Does not record when Pr.06-73=3 and uC displays Warning”.
Cause Corrective Actions
Broken motor cable Exclude the connection issue of the motor and its load.
Improper setting for the low
current protection
Set the proper settings for Pr.06-71, Pr.06-72 and Pr.06-73.
Low load
Check the loading status.
Make sure the loading matches the motor capacity.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
BrandDelta
ModelC2000 Plus Series
CategoryDC Drives
LanguageEnglish

Related product manuals