Chapter 13 Warning CodesC2000 Plus
13-19
ID No. Display on LCD Keypad Warning Name Description
18
Deviation Warning
(dAvE)
Over speed deviation warning
Action and Reset
Action condition Pr.10-13
Action time Pr.10-14
Warning setting parameter
Pr.10-15=0
0: Warn and keep operation
Reset method Warningautomatically clears when the drive stops
Reset condition After the drive stops
Record N/A
Cause Corrective Actions
Improper parameter setting for the
slip error
Reset proper value for Pr.10-13 and Pr.10-14.
Improper setting for ASR
parameter and acceleration/
deceleration
Reset ASR parameters.
Set proper accel./ decel. time.
Accel./ Decel. time is too short Reset proper accel./ decel. time.
Motor locked Remove the causes of motor locked.
Mechanical brake is not released Check the active timing of the system.
Incorrect parameter setting of
torque limit
(Pr.06-12, Pr.11-1720)
Adjust to proper setting value.
Malfunction caused by
interference
Verify wiring of the control
circuit, and wiring/grounding of the main circuit to
prevent interference.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
AltitudeUp to 1000m without derating
CommunicationCANopen
Output Current2.5A
Protection FeaturesOvercurrent, Overvoltage, Overtemperature
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Humidity95% RH (non-condensing)