Chapter 13 Warning CodesC2000 Plus
13-26
ID No. Display on LCD Keypad Warning Name Description
24
Over slip warning
(oSL)
Over slip warning.
By using the maximum slip (Pr.10-
29) as the base, when
the drive outputs at constant speed, and the F>H or F<H
exceeds Pr.07-29 level and Pr.07-30 set
ting time, 100%
Pr.07-29 = Pr.10-29.
Action and Reset
Action condition
When the drive outputs at constant speed, and F>H or F<H exceeds the Pr.07-
29 level
Action time Pr.07-30
Warning setting parameter
Pr.07-31=0 Warning
0: Warn and keep operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning
Reset method
When Pr.07-31=0 and
when the drive outputs at constant speed, and F>H or F<H
no longer exceeds the Pr.07-29 level, the oSL warning automatically clears.
Reset condition N/A
Record N/A
Cause Corrective Actions
Check if the motor parameter is
correct
Check the motor parameter.
The load is too large Decrease the loading.
Check if the settings for Pr.07-29,
Pr.07-30 and Pr.10-29 are
properly
set
Check the parameter settings for oSL protection.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
BrandDelta
ModelC2000 Plus Series
CategoryDC Drives
LanguageEnglish

Related product manuals