Chapter 13 Warning CodesC2000 Plus
13-28
ID No. Display on LCD Keypad Warning Name Description
28
Output phase loss
(OPHL)
Output phase loss
Action and Reset
Action condition Pr.06-47
Action time N/A
Warning setting parameter
Pr.06-45
0: Warn and keep operating
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning
Reset method
If
Pr.06-45 is set to 0, the OPHL warning automatically clears after the drive stops.
Reset condition N/A
Record N/A
Cause Corrective Actions
Unbalanced three-phase
impedance of the motor
Replace the motor.
Check if the wiring is incorrect
Check the cable.
Replace the cable.
Check if the motor is a single-
phase motor
Choose a three-phase motor.
Check if the current sensor is
broken
Check if the control board cable is loose. If yes, reconnect the cable and run
the
drive to test. If the error still occurs, return to the factory for repair.
Check if the three-phase current is balanced with a current clamp meter. I
f the
current is balanced and the OPHL error still shows on the display,
return to the
factory for repair.
If capacity of the drive is larger
than the motor
Choose the matches capacity of the drive and motor.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
BrandDelta
ModelC2000 Plus Series
CategoryDC Drives
LanguageEnglish

Related product manuals