EasyManua.ls Logo

Delta C2000 Plus Series - Page 845

Delta C2000 Plus Series
1259 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 13 Warning CodesC2000 Plus
13-44
ID No. Display on LCD Keypad Warning Name Description
52
Data defect (PLdA) Data error during PLC operation
Action and Reset
Action condition
The program detects incorrect write-
in address when translating the program
source code, then PLSv warning acts.
Action time Immediately displays when the fault is detected
Warning setting parameter N/A
Reset method
Check if the program is correct and re-download the program. If the
fault does
not exist, the warning automatically clears.
Reset condition N/A
Record N/A
Cause Corrective Actions
During PLC operation, the external
Modbus has written/read incorrect
data to internal PLC program
Check if the upper unit transmits the correct command
The built-
in PLC function is ON,
there is station address of
Modbus which is duplicate of
the built-
in PLC station address
(Pr.09-35) been set in the
Modbus system of the
equipment
Set the station addresses of Modbus and built-in PLC to be different

Table of Contents

Related product manuals