EasyManuals Logo
Home>Delta>DC Drives>C2000 Plus Series

Delta C2000 Plus Series User Manual

Delta C2000 Plus Series
1259 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #851 background imageLoading...
Page #851 background image
Chapter 13 Warning CodesC2000 Plus
13-50
ID No. Display on LCD Keypad Warning Name Description
58
PLC MCR error
(PLCr)
PLC MCR command error
Action and Reset
Action condition
The MC command is detected during PLC operation,
but there is no
corresponded MCR command, then the PLCr warning shows.
Action time Immediately displays when the fault is detected
Warning setting parameter NA
Reset method
Check if the program is correct and re-download the program. If the
fault does
not exist, the warning automatically clears.
Reset condition N/A
Record N/A
Cause Corrective Actions
The MC command is continuously
used for more than 9 times
The MC command cannot be used continuously for 9 times. Check and reset
the
program, then re-download the program.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
BrandDelta
ModelC2000 Plus Series
CategoryDC Drives
LanguageEnglish

Related product manuals