Chapter 13 Warning CodesC2000 Plus
13-53
ID No. Display on LCD Keypad Warning Name Description
61
CAN/M guarding error
(PCGd)
CANopen Master guarding error
Action and Reset
Action condition
When CANopen Master Node Guarding detects that one of the Slaves does not
response, the PCGd warning will display
Action time Immediately displays when the fault is detected
Warning setting parameter NA
Reset method
Check if the program is correct and re-download the program. If the
fault does
not exist, the warning automatically clears.
Reset condition N/A
Record N/A
Cause Corrective Actions
Slave is not connected or
CANopen BUS cable is not
connected
Connect the Slave and CANopen BUS
Malfunction caused by
interference
1. Verify wiring/grounding of the
communication circuit. It is recommended to
separate the communication circuit from the main circuit
, or wire in 90 degree
for effective anti-interference performance.
2. Make sure the communication circuit is wired in series.
3. Use CANopen cable or add terminating resistance.
Communication cable is broken or
bad connected
Check or replace the communication cable.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
BrandDelta
ModelC2000 Plus Series
CategoryDC Drives
LanguageEnglish

Related product manuals