Chapter 13 Warning CodesC2000 Plus
13-88
ID No. Display on LCD Keypad Warning Name Description
101
InrCOM time-out (ictn) Internal communication time-out
Action and Reset
Action condition
When Pr.09-31=(-1) (-10) (no -9) and the internal
communication between
Master and Slave is abnormal, the ictn warning shows.
Action time Immediately acts
Warning setting parameter N/A
Reset method Auto-reset
Reset condition
The warning automatically clears when the communication is back to normal
condition
Record N/A
Cause Corrective Actions
Malfunction caused by
interference
Verify wiring/grounding of the communication circuit.
It is recommended to
separate the communication circuit from the main
circuit, or wire in 90 degree for
effective anti-interference performance.
Different communication
conditions with the upper unit
Check if the setting for Pr.09-04 is the same as the setting for upper unit
Communication cable break off or
not connected well
Check the cable status or replace the cable

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
AltitudeUp to 1000m without derating
CommunicationCANopen
Output Current2.5A
Protection FeaturesOvercurrent, Overvoltage, Overtemperature
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Humidity95% RH (non-condensing)

Related product manuals