Chapter 14 Fault Codes and DescriptionsC2000 Plus
14-63
ID* Display on LCD Keypad Fault Name Fault Descriptions
61
Y-connection / Δ-
connection
switch fault
(ydc)
A fault occurs when
Y-Δ switches
Action and Reset
Action condition
1. ydc occurs when the confirmation signals of Y-connection and Δ-
connection
are conducted at the same time.
2. If any of confirmation signals is not conducted within Pr.05-25, ydc occurs.
Action time Pr.05-25
Fault treatment parameter N/A
Reset method Manual reset
Reset condition
Can be reset only when the confirmation signal of Y-
connection is conducted if it
is Y-connection, or when the confirmation signal of Δ-
connection is conducted if
it is Δ-connection.
Record Yes
Cause Corrective Actions
The electromagnetic valve
operates incorrectly during Y-Δ
switch.
Check if the electromagnetic valve works normally.
If not, replace it.
Incorrect parameter setting Check if related parameters are all set up and set correctly.
The wiring of Y-Δ
switch function is
incorrect
Check the wiring.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
AltitudeUp to 1000m without derating
CommunicationCANopen
Output Current2.5A
Protection FeaturesOvercurrent, Overvoltage, Overtemperature
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Humidity95% RH (non-condensing)

Related product manuals