EasyManua.ls Logo

Delta CP2000 Series

Delta CP2000 Series
868 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 12 Description of Parameter SettingsCP2000
12.1-00-15
The default for the frequency source or operation source is AUTO mode. It returns to AUTO
mode whenever you cycle the power. If you use a multi-function input terminal to switch AUTO /
HAND mode, the multi-function input terminal has the highest priority. When the external terminal
is OFF, the drive does not accept any operation signal and cannot execute JOG.
Digital Keypad STOP Function
Default: 0
Settings 0: STOP key disable
1: STOP key enable
This parameter is valid when the digital keypad is not set as the operation command source
(Pr.00-21≠0). When Pr.00-21=0, the STOP key on the digital keypad is not affected by this
parameter.
Display Filter Time (Current)
Default: 0.100
Settings: 0.001–65.535 sec.
Minimizes the current fluctuation displayed by digital keypad.
Display Filter Time (Keypad)
Default: 0.100
Settings: 0.001–65.535 sec
Minimizes the value fluctuation displayed by digital keypad.
Software Version (date)
Default: Read only
Settings: Read only
Displays the current drive software version by date.

Table of Contents

Other manuals for Delta CP2000 Series

Related product manuals