Chapter 12 Description of Parameter SettingsCP2000
12.1-02-5
Settings Functions Descriptions
11
B.B. input from external
(B.B.: Base Block)
ON: the output of the drive stops immediately. The motor is in free
run and the keypad displays the B.B. signal. Refer to Pr.07-08 for
details.
12
Output Stop
(Output pause)
When the switch is ON, output of the drive stops immediately and
the motor is in free run status. The drive is in output waiting status
until
the switch is turned to OFF, and then the drive restarts and
runs to the current setting frequency.
13
Cancel the setting for
auto-acceleration /
auto-deceleration time
Set Pr.01-44 to one of the Pr.01-04 setting modes before using this
function. When this function is enabled, OFF is for auto mode and
ON is for linear acceleration / deceleration.
14
Switch between motor 1
and motor 2
ON: use parameters for motor 2 .
OFF: use parameters for motor 1.
15
Rotating speed
command from AVI1
ON: force the source of the frequency to be AVI1. (If the rotating
speed commands are set to AVI1, ACI and AVI2 at the same time,
the priority is AVI1ACIAVI2)
16
Rotating speed
command form ACI
ON: force the source of the frequency to be ACI. (If the rotating
speed commands are set to AVI1, ACI and AVI2 at the same time.
The priority is AVI1ACIAVI2)
17
Rotating speed
command form AVI2
ON: force the source of the frequency to be AVI2. (If the rotating
speed commands are set to AVI1, ACI and AVI2 at the same time.
The priority is AVI1ACIAVI2)
18 Forced to stop (Pr.07-20) ON: the drive ramps to stop according to Pr.07-20 setting.
19
Digital Up command
ON: the frequency of the drive increases or decreases by one unit.
If this function remains ON continuously, the frequency increases
or decreases according to Pr.02-09 / Pr.02-10.
The Frequency command returns to zero when the drive stops, and
the displayed frequency is 0.0 Hz. If you select Pr.11-00, bit7 = 1,
the frequency is not saved.
20
Digital Down command
21
PID function disabled ON: the PID function is disabled.
22 Clear the counter
ON: the current counter value is cleared and displays “0”. The drive
counts up when this function is disabled.

Table of Contents

Other manuals for Delta CP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta CP2000 Series and is the answer not in the manual?

Delta CP2000 Series Specifications

General IconGeneral
Output Voltage0 ~ Input Voltage
Communication InterfaceRS-485
Storage Temperature-20°C to 60°C
Input Voltage200-240V AC, 380-480V AC
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit

Related product manuals