Chapter 12 Description of Parameter SettingsCP2000
12.1-02-17
02-13,02-14,
02-36,02-37,
Fcmd=60Hz
02-22=10Hz
02-23=2Hz
02-24=40Hz
02-25=2Hz
H
38Hz
40Hz
42Hz
10Hz
12Hz
8Hz
T
=3
02-13,02-14,
02-36,02-37,
=4
Brake Delay Time
Default: 0.000
Settings 0.000–65.000 sec.
When the AC motor drive runs after the setting delay time of Pr.02-32, the corresponding
multi-function output terminal (12: mechanical brake release) is “closed”. The function must be
used with DC brake.
This parameter is invalid if it is used without DC brake. Refer to the following operation timing.