EasyManua.ls Logo

Delta CP2000 Series

Delta CP2000 Series
868 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 12 Description of Parameter SettingsCP2000
12.1-02-18
Output Current Level Setting for Multi-function Output Terminals
Default: 0
Settings 0–150%
When the drive outputs current higher than or equal to Pr.02-33, the multi-function output
parameters active (Pr.02-13, Pr.02-14, and Pr.02-15 are set to 27).
When the drive outputs current lower than Pr.02-33, the multi-function output parameters active
(Pr.02-13, Pr.02-14, and Pr.02-15 are set to 28).
Output Frequency Setting for Multi-function Output Terminals
Default: 3.00
Settings 0.00–599.00 Hz
When the drive outputs frequency higher than or equal to Pr.02-34 (actual output frequency H
Pr.02-34), the multi-function terminal active (Pr.02-13, Pr.02-14 and Pr.02-15 are set to 29).
When the drive outputs frequency lower than Pr.02-34 (actual output frequency H < Pr.02-34), the
multi-function terminals active (Pr.02-13, Pr.02-14 and Pr.02-15 are set to 30).
External Operation Control Selection after Reset and Activate
Default: 0
Settings 0: Disable
1: Drive runs if the RUN command remains after reset or re-boot
Setting 1: the driver automatically executes the RUN command under the following
circumstances, pay extra attention on this.
Status 1: After the drive is powered on and the external terminal for RUN stays ON, the drive
runs.
Status 2: After clearing a fault once a fault is detected and the external terminal for RUN
stays ON, you can run the drive by pressing RESET key.
Display the Status of Multi-function Input Terminal
Default: Read only
Settings Monitoring status of multi-function input terminal

Table of Contents

Other manuals for Delta CP2000 Series

Related product manuals