EasyManua.ls Logo

Delta CP2000 Series

Delta CP2000 Series
868 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 12 Description of Parameter SettingsCP2000
12.1-03-19
Example 1, AFM2 0–10 V is set to the output frequency, the output equation is:
10 V * (output frequency / Pr.01-00) * Pr.03-24 + 10 V * Pr.03-27
Example 2, AFM2 0–20 mA is set to the output frequency, the output equation is:
20 mA*(output frequency / Pr.01-00) * Pr.03-24 + 20 mA * Pr.03-27
Example 3, AFM2 4–20 mA is set to the output frequency, the output equation is:
4 mA+16 mA * (output frequency / Pr.01-00) * Pr.03-24 + 16 mA * Pr.03-27
This parameter sets the corresponding voltage for the analog output 0.
AVI1 Terminal Input Selection
Default: 0
Settings 0: 0–10 V
1: 0–20 mA
2: 4–20 mA
ACI Terminal Input Selection
Default: 0
Settings 0: 4–20 mA
1: 0–10 V
2: 0–20 mA
When you change the input mode, verify that the external terminal switch (SW3, SW4)
corresponds to the setting for Pr.03-28–Pr.03-29.
PLC Analog Output Terminal Status
Default: Read only
Settings Monitor the status of PLC analog output terminals
P.03-30 displays the external multi-function output terminal that used by PLC.
For Example:
When Pr.03-30 displays 0002h (hex), it means that AFM2 is used by PLC.

Table of Contents

Other manuals for Delta CP2000 Series

Related product manuals