Chapter 12 Description of Parameter SettingsCP2000
12.1-06-32
When in fire mode, the skip frequency function is not available.
When in fire mode, the operating frequency for Pr.06-81 cannot be larger than Pr.01-00
Maximum Output Frequency. If Pr.06-81 > Pr.01-00, the maximum frequency is automatically set
to Pr.01-00.