Chapter 12 Description of Parameter SettingsCP2000
12.1-06-31
When in fire mode, the running direction of the drive is based on Pr.06-08=1 (FWD) or
Pr.06-80=2 (REV). Other running direction commands are invalid and Pr.00-23 Motor Operating
Direction is not available when in fire mode.
When in fire mode, all keypad command are ignored, including RUN, STOP, JOG and direction
commands.
When in fire mode, all RS-485 communication commands are ignored, including RUN, STOP,
JOG and direction commands.
When in fire mode, B.B. and EF are not activated, including external terminal B.B,
communication B.B, external terminal EF, communication EF and external terminal EF1). Any
activated B.B. is automatically invalid, including external terminal B.B. and communication B.B.,
and the drive executes speed tracking.
When in fire mode, activated EF and EF1 are automatically invalid, including external terminals
EF & EF1 and communication EF).
When in fire mode, the JOG command is not available (JOG command source: keypad, external
terminals and communications). Any operating JOG command is automatically invalid.
When in fire mode, the Acceleration / Deceleration Speed Inhibit function is not available. Any
activated acceleration / deceleration speed inhibition is automatically invalid.
When in fire mode, If you set Pr.06-86 to bit0=0 (open-loop control), the drive does not execute
parameter group 08 PID function. Any operating PID function is automatically invalid.
When in fire mode, the Hand-Off-Auto function is not available, including multi-function output
terminals.
When in fire mode, the drive does not execute the circulative control function, and all circulating
control function parameters are cleared. The circulative control function is automatically invalid
when in fire mode.
When in fire mode, the drive does not execute the sleep function.
When in fire mode, the drive does not execute the DC brake function. Any operating DC brake is
automatically invalid when in fire mode.
When in fire mode, the drive does not execute over-current stall prevention function. Any
operating over-current stall prevention is automatically invalid when in fire mode.
When in fire mode, over-torque detection function is not available.
When in fire mode, OL1/OL2 detection function is not available.
When in fire mode, abnormal communication (CE10, CE1, CE2, CE3 and CE4) detection is not
available.
The cd1, cd2, cd3 and Hd0, Hd1, Hd2, Hd3 are boot check and cannot be cleared. The above
errors cannot be cleared when in fire mode. The drive does not operate when in fire mode.
Lv protection is not activated when in fire mode, so the drive keeps running or runs until the
power is lost. If the Lv error occurs before the fire mode warning, clear the Lv error to operate the
drive.
If bypass fire mode indication (MOx=54) is activated, reboot the drive and deactivate the fire
mode to turn off this terminal output.
When in fire mode, the output stop function is not available.

Table of Contents

Other manuals for Delta CP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta CP2000 Series and is the answer not in the manual?

Delta CP2000 Series Specifications

General IconGeneral
Output Voltage0 ~ Input Voltage
Communication InterfaceRS-485
Storage Temperature-20°C to 60°C
Input Voltage200-240V AC, 380-480V AC
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit

Related product manuals