Chapter 12 Description of Parameter SettingsCP2000
12.1-12-11
However, if the flow quantity or pressure is too large, the CP2000 stops, one by one, the motors use
mains electricity until the CP2000 decreases the main motor’s frequency to 0 Hz. See Diagram
12-10 and Diagram 12-11.
Diagram 12-10: Sequence of Fixed Quantity Control with PID – Decreasing Demand