Chapter 17 Introduction to BACnet │CP2000
17-12
Commandable Analog Value Object
In VFD-CP2000, we have AV_000–AV_026 supporting commandable Present_Value property. In
these AV_Objects, we also can use (Multi) Read_Service to access Priority_Array and
Relinquish_Default properties.
Object
Number
R/W Object Name Object Description Unit
AV 000 RW AV_000_Reserved Reserved UNITS_NO_UNITS
AV 001 RW AV_001_FreqRefValue Frequency Reference Value UNITS_HERTZ
AV 002 RW AV_002_Reserved Reserved UNITS_NO_UNITS
AV 003 RW AV_003_Reserved Reserved UNITS_NO_UNITS
AV 004 RW AV_004_Reserved Reserved UNITS_NO_UNITS
AV 005 RW AV_005_Reserved Reserved UNITS_NO_UNITS
AV 006 RW AV_006_Reserved Reserved UNITS_NO_UNITS
AV 007 RW AV_007_Reserved Reserved UNITS_NO_UNITS
AV 008 RW AV_008_Reserved Reserved UNITS_NO_UNITS
AV 009 RW AV_009_Reserved Reserved UNITS_NO_UNITS
AV 010 RW AV_010_Reserved Reserved UNITS_NO_UNITS
AV 011 RW AV_011_P9-11 map set= ----- AV11 will modify data which is P9-11 mapping to Depends
AV 012 RW AV_012_P9-12 map set= ----- AV12 will modify data which is P9-12 mapping to Depends
AV 013 RW AV_013_P9-13 map set= ----- AV13 will modify data which is P9-13 mapping to Depends
AV 014 RW AV_014_P9-14 map set= ----- AV14 will modify data which is P9-14 mapping to Depends
AV 015 RW AV_015_P9-15 map set= ----- AV15 will modify data which is P9-15 mapping to Depends
AV 016 RW AV_016_P9-16 map set= ----- AV16 will modify data which is P9-16 mapping to Depends
AV 017 RW AV_017_P9-17 map set= ----- AV17 will modify data which is P9-17 mapping to Depends
AV 018 RW AV_018_P9-18 map set= ----- AV18 will modify data which is P9-18 mapping to Depends
AV 019 RW AV_019_P9-19 map set= ----- AV19 will modify data which is P9-19 mapping to Depends
AV 020 RW AV_020_P9-20 map set= ----- AV20 will modify data which is P9-20 mapping to Depends
AV 021 RW AV_021_P9-21 map set= ----- AV21 will modify data which is P9-21 mapping to Depends
AV 022 RW AV_022_P9-22 map set= ----- AV22 will modify data which is P9-22 mapping to Depends
AV 023 RW AV_023_P9-23 map set= ----- AV23 will modify data which is P9-23 mapping to Depends
AV 024 RW AV_024_P9-24 map set= ----- AV24 will modify data which is P9-24 mapping to Depends
AV 025 RW AV_025_P9-25 map set= ----- AV25 will modify data which is P9-25 mapping to Depends
AV 026 RW AV_026_P9-26 map set= ----- AV26 will modify data which is P9-26 mapping to Depends

Table of Contents

Other manuals for Delta CP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta CP2000 Series and is the answer not in the manual?

Delta CP2000 Series Specifications

General IconGeneral
Output Voltage0 ~ Input Voltage
Communication InterfaceRS-485
Storage Temperature-20°C to 60°C
Input Voltage200-240V AC, 380-480V AC
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit

Related product manuals