Chapter 17 Introduction to BACnet │CP2000
17-11
The Properties of Objects
Property ID
Object Type
Device Analog Value Binary Value
#4 ACTIVE TEXT V
#11 APDU_TIMEOUT V
#12 APPLICATION_SOFTWARE_VERSION V
#28 DESCRIPTION V V V
#30 DEVICE ADDRESS BINDING V V
#36 EVENT STATE V V
#44 FIRMWARE_REVISION V
#46 INACTIVE TEXT V
#62 MAX_APDU_LENGTH_ACCEPTED V
#63 MAX_INFO_FRAMES V
#64 MAX_MASTER V
#70 MODEL_NAME V
#73 NUMBER_OF_APDU_RETRIES V
#75 OBJECT_IDENTIFIER
V *1
V V
#76 OBJECT_LIST V
#77 OBJECT_NAME
V *1
V V
#79 OBJECT_TYPE V V V
#81 OUT OF SERVICE V V
#85 PRESENT VALUE
V *2 V *2
#87 PRIORITY ARRAY V *3 V *3
#96 PROTOCOL_OBJECT_TYPES_SUPPORTED V
#97 PROTOCOL_SERVICES_SUPPORTED V
#98 PROTOCOL_VERSION V
#104 RELINQUISH DEFAULT V *3 V *3
#107 SEGMENTATION_SUPPORTED V
#111 STATUS FLAGS V V
#112 SYSTEM_STATUS V
#117 UNITS V
#120 VENDOR_IDENTIFIER V
#121 VENDOR_NAME V
#139 PROTOCOL_REVISION V
#155 DATABASE_REVISION V
*1. The Object_ID and Object_Name Properties of Device are writeable.
*2. The Present_Value Property of some AV and BV objects are commandable.
*3. Only Commandable objects support Priority_Array and Relinquish_Default.

Table of Contents

Other manuals for Delta CP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta CP2000 Series and is the answer not in the manual?

Delta CP2000 Series Specifications

General IconGeneral
Output Voltage0 ~ Input Voltage
Communication InterfaceRS-485
Storage Temperature-20°C to 60°C
Input Voltage200-240V AC, 380-480V AC
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit