Chapter 17 Introduction to BACnet │CP2000
17-15
Status (Readonly) Binary Value Object
In VFD-CP2000, we have BV_016–BV_031 with read-only Present_Value property. In these
BV_Objects, we do NOT have Priority_Array and Relinquish_Default properties.
Object
Number
R/W Object Name Object Description
BV 016 R BV_016_ARRIVE STATE (0)Not yet;(1)Arrive (OutputFreq=FreqCmd)
BV 017 R BV_017_FWD/REV STATE (0)Forward;(1)Reverse
BV 018 R BV_018_WARN STATE (0)No Warn;(1)Occur Warn
BV 019 R BV_019_ERROR STATE (0)No Error;(1)Occur Error
BV 020 R BV_020_Reserved Reserved
BV 021 R BV_021_Reserved Reserved
BV 022 R BV_022_QSTOP STATE (0)No QSTOP;(1)Occur QSTOP
BV 023 R BV_023_ServoPower STATE (0)PowerOff(free run to stop);(1)PowerOn
BV 024 R BV_024_Reserved Reserved
BV 025 R BV_025_Reserved Reserved
BV 026 R BV_026_Reserved Reserved
BV 027 R BV_027_Reserved Reserved
BV 028 R BV_028_Reserved Reserved
BV 029 R BV_029_Reserved Reserved
BV 030 R BV_030_Reserved Reserved
BV 031 R BV_031_Reserved Reserved

Table of Contents

Other manuals for Delta CP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta CP2000 Series and is the answer not in the manual?

Delta CP2000 Series Specifications

General IconGeneral
Output Voltage0 ~ Input Voltage
Communication InterfaceRS-485
Storage Temperature-20°C to 60°C
Input Voltage200-240V AC, 380-480V AC
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit

Related product manuals