Chapter 1 Introduction 
1-3 
1.1  Specification 
DVP02TK-S/DVP02TU-S 
Supply voltage 
24VDC   
Max. rated power 
2.4W, supplied by external power source in compliance with UL61010-2-201 \ IEC61131-2  
Connector Type 
European standard removable terminal block (Pin pitch: 3.5mm) 
Operation/storage 
temperature 
Operation: 0°C ~ 55°C (temperature), 5 ~ 95% (humidity), Pollution degree: 2 
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity), Attitude: up to 2000m; 
For use in dry location only 
Vibration/Shock 
resistance 
International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc) / IEC 61131-2 & IEC 68-2-27 
(TEST Ea) 
Connection to 
The modules are numbered from 0 to 7 automatically by their distance from DVP-PLC. Max. 8 
modules are allowed to connect to DVP-PLC and will not occupy any digital I/O points. 
I/O points 
2 points of universals analog inputs (CH1, CH2), 2 analog outputs (OUT1, OUT2) or 4 digital 
outputs (OUT1~OUT4) 
General Analog Input 
Input 
CH1,   
CH2 
Thermal resistance: Pt100, JPt100, Pt1000, Ni100, Ni120, Ni1000, Cu50, Cu100, LG-Ni1000 
Thermocouple : J, K, R, S, T, E, N, B, U, L, TXK (L), C, PL II 
Voltage input: 0~+50mV, 100~+100mV, 0~+5V, 0~+10V 
Current input: 0mA~+20mA, 4~+20 mA 
16 bits 
Distance 
100 meters 
Input disconnection 
detection   
Supported by exceeded temperature input range   
Analog / Digital Output 
Analog 
OUT1~ 
OUT2 
Analog output, 12-bit: 0~+10V, 0/4~+20mA 
Digital 
OUT1~ 
4 channels digital output, 250VAC, 60Hz/24VDC, 2A, Relay 
4 channels digital output, Voltage pulse output, 24VDC, 300mA 
 
  A/D Function Specification   
Analog / Digital  Voltage Input 
Maximum rated input 
0V~10V  0V~5V 
Overall accuracy 
(normal temperature) 
±0.5% 
Overall accuracy 
(full temperature range) 
±1% 
Hardware resolution 
16 bits 
Input impedance 
650KΩ