InfraSuite EnviroStation 43
Event Type: Allows you to individually determine sensor alarm levels.
Reactions will only be triggered when Warning or Alarm is selected.
Title: You can entitle devices for identification.
Power Configuration: If Normal Open is selected, the EnviroStation
supplies 12Vdc or 24Vdc power to Sensor HUB. If Manual is selected and
Off button is clicked, the power is cut off. You can also set up Reaction
(please see 5-2-1 Management- Reaction) to automatically cut off the
power. Power is cut off during the period of time specified in the Active
Period box. Power resumes after the given duration. If the specified Active
Period is 0, power does not resume.
Digital Input
NO/ NC: If Normal Open is selected, an event is triggered when 1. Dry
Contact is closed, or 2. Wet Contact is provided with 5~24Vdc. If Normal
Close is selected, an event is triggered when 1. Dry Contact is open, or 2.
Wet Con-tact is provided with < 1.5Vdc.
Digital Value Dry Contact Wet Contact
1 Close 5~24Vdc
0 Open < 1.5Vdc
Event Type: Allows you to individually determine the Alarm levels for
sensors. Selecting Alarm or Warning triggers reactions.
Title: You can entitle devices for identification.