InfraSuite EnviroStation 47
For EnviroProbe 1200 (EMS1200)
The EnviroProbe 1200 (EMS1200) provides two analog inputs, one analog
output and one water-leakage detection. In this page, select an ID first and
then set up Title and Type. Click Enable if you wish to enable the device.
Please note that the ID means the ID No. you set up for your EnviroProbe
1200 (EMS1200) using its ID DIP switches (please see 3.3 EnviroProbe).
You can set up the following:
1) Analog Input
Set up each analog input’s ((ADC-a)*b/c-d), Title and Event Settings.
Click the color bar in Event Settings to change event types for different
thresholds of analog inputs. Green, yellow, and red mean normal,
warning, and alarm events respectively.
2) Leakage
Set up leakage’s Sensitivity, Title and Event Type. If you check the
Buzzer Enable box, the EnviroProbe 1200 (EMS1200) will enable
buzzer when it detects water leakage.
3) Analog Output
Set up analog output (Automatic or Manual), Title and Control. If
Manual is selected, Reaction (please see 5.2.1 Management -
Reaction) won’t be able to control analog output.