8.3 Remote Monitor
The optional remote monitor can be connected to the UPS via the built-in RS-485
interface, and the UPS operating status can be transmitted to the remote control
room via the RS-485 interface for users to realize centralized monitoring.
8.4 Monitoring Software
Via the built-in RS-232 port and UPSentry 2012 software (http://www.
deltapowersolutions.com/en/mcis/software-center.php), users can monitor and
manage the UPS remotely.
8.5 Battery Start-up
When there is no AC power and you wish to start up the UPS, please refer to
Chapter 7.2.2 and Chapter 7.2.6. If the AC power is still not recovered, the UPS will
shut down after the batteries are fully discharged.
8.6 ECO Mode
Choose ECO mode from the LCD to let the UPS work in ECO Mode. When the
UPS is running in ECO mode, it is the reserve AC power to supply power to the
connected loads. If the reserve AC power is abnormal, the connected loads will
be power-supplied by the inverter. ECO mode is only applicable to the UPS with
capacity above 260kVA (included). For the capacity below 200kVA (included), the
function of ECO mode is optional.