Chapter 7 UPS Operation
88
 ,IWKHEDWWHU\WHVWLVQRUPDOXVHDYROWDJHPHWHUWRPHDVXUHWKH836¶VRXWSXW
voltage (per phase). If normal, turn on the UPS Output breaker or switch.
7.2.2 Battery Mode Start-up Procedures (Single)
NOTE :
1. Before executing the following start-up procedures, please refer to 7.1
3UH6WDUWXS3UH7XUQR௺:DUQLQJV¿UVW
2. Battery start function is customized and only applicable to the model that
has the built-in battery contactor.
 7XUQRQHDFKH[WHUQDOEDWWHU\FDELQHW¶VBattery breaker.
2. Press the battery start-up switch once.
 $IWHUWKH'&%86YROWDJHUHDFKHVDURXQG9WKH836¶VEDWWHU\FRQWDFWRUZLOO
start up.
4. Press the ONDQGµ
¶EXWWRQVVLPXOWDQHRXVO\IRUVHFRQGV$IWHUWKDWWKH
inverter will start up, the inverter voltage will be established and the LCD will
display ‘Backup Mode¶
5. Measure the voltage of the UPS Output breaker or switch. If normal, turn on the
UPS Output breaker or switch.
7.2.3 Manual Bypass Mode Start-up Procedures (Single)
NOTE :
 5HJXODU836PDLQWHQDQFHDWDIUHTXHQF\RIHYHU\KDOI\HDULVVXJJHVWHG
2. Before executing the following procedures, please refer to 7.1 Pre Start-
XS3UH7XUQR௺:DUQLQJV¿UVW
The Manual Bypass breaker or switch can only be turned ON for UPS
PDLQWHQDQFHZKLFKHQVXUHVWKDWWKHSRZHUVXSSO\LQJWRWKHFRQQHFWHGORDGVZRQ¶W
be interrupted during maintenance process.
If the Manual Bypass breaker or switch is turned ON in Normal Mode, the inverter
will be turned OFF, the connected critical loads will be power-supplied by the
PDQXDOE\SDVVDQGWKHRXWSXWZRQ¶WEHSURWHFWHG3OHDVHHQVXUHWKDWWKHUHVHUYH
AC power is normal.