103
Ultron NT Series
Power rating kVA (P.F.=0.9) 10 15 20 30 40 50 60 80 100 120 160 200 260 320 400 500
Complete system
2YHUDOOHႈFLHQF\
Normal mode
(400/230V)
%8889909191
91.5 91.5
92 92
92.5 92.5 92.5 92.5 92.5 92.5
93
Inverter overload 110% : 60min 125% : 10min 150% : 1min
Static switch overload current:
30 minutes % 120
30 milliseconds % 1000
Transfer time
m
sec
c
0
Ambient temperature °C 0~40
Relative humidity
(no condensate)
%90
Operating elevation m 0~2000 ( 0~6060 ft )
Audible noise
(at a distance of 1.5m)
    
Dimensions : (Model 400/230Vac only)
width mm
600 800 1200 1600
800
+1100
depth mm
800 830 830 995 995
height mm
1400 1700 1700 1950 1950
Weight kg
335 335 365 365 425 460 506 525 700 745 1050 1085 1680 1720 1920 2410
NOTE :
1.
*
1
: 220, 230, 240 (1 2W +G) single phase output voltage for model
20kVA~60kVA only.
 $OOWKHZHLJKWDQGGLPHQVLRQVOLVWHGLQWKHDERYHVSHFL¿FDWLRQVDUHIRU
models with the 6-pulse rectifier. For models that install the 12-pulse
rectifier and any other customized models, please contact your local
dealer, sales representative or Delta customer service for their weight and
dimensions.
3. Please refer to the rating label for the safety rating.
 $OOVSHFL¿FDWLRQVDUHVXEMHFWWRFKDQJHZLWKRXWSULRUQRWLFH