Loading...
51
Ultron NT Series
UPS
Capacity
(VA)
I/P
Voltage
(V)
O/P
Voltage
(V)
I/P
C.B.
(A)
I/P
Cable
(mm²)
RES
C.B.
(A)
RES
Cable
(mm²)
O/P
C.B.
(A)
O/P
Cable
(mm²)
BAT.
Cable
(mm²)
BAT.
Fuse
(A)
GND.
Cable
(mm²)
120K
120/ 208 120/ 208 500 80*2 400 150 400 150
125 400 80
220/ 380 220/ 380 300 100 225 80 225 80
277/ 480 277/ 480 225 80 175 50 175 50
220/ 380 220 300 100 800 125*2 800 125*2
160K
120/ 208 120/ 208 800 125*2 630 100*2 630 100*2
100*2 600 80220/ 380 220/ 380 350 125 300 100 300 100
277/ 480 277/ 480 300 100 250 100 250 100
200K
120/ 208 120/ 208 1000 150*2 800 125*2 800 125*2
125*2 600 125220/ 380 220/ 380 500 80*2 400 150 400 150
277/ 480 277/ 480 350 150 300 100 300 100
260k
220/ 380 220/ 380 630 100*2 500 80*2 500 80*2
150*2 800 150
277/ 480 277/ 480 500 80*2 400 150 400 150
320k
220/380 220/380 800 125*2 630 100*2 630 100*2
125*3 1000 180
277/ 480 277/ 480 630 100*2 500 80*2 500 80*2
400k
220/380 220/380 1000 150*2 800 125*2 800 125*2
150*3 1200 240
277/480 277/480 800 125*2 630 100*2 630 100*2
500K
220/ 380 220/ 380 1250 100*4 1000 150*2 1000 150*2
150*4 1600 300
277/ 480 277/ 480 1000 150*2 800 125*2 800 125*2
* The cable rating above is based on 105°C PVC type.
** Please follow local regulations to install suitable cables and circuit breakers.
UPS Rated
VA
I/P Voltage
(V)
O/P Voltage
(V)
RECTIFIER
Fuse ( A )
INVERTER
Fuse ( A )
RESERVE
Fuse ( A )
BATTERY
Fuse ( A )
260k
220/380 220/380
315NHG2B
660GH-315A
FWH-300A
A50QS800-4 A50QS800-4
277/480 277/480
320k
220/380 220/380
400NHG2B FWH-400A A50QS1000-4 A50QS1000-4
277/480 277/480
400k
220/380 220/380
500NHG3B FWH-400A A50QS1000-4 A50QS1200-4
277/480 277/480
500K
220/380 220/380
630NHG3B FWH-600A A50QS1200-4
FWH-1600A
A50QS800-4*2
277/480 277/480

Table of Contents