105
Installation and Operation Manual for Inverter RPI M50A_12s V1 EU EN 2017-03-09
8 Settings
8.4.12 Loading the factory settings
Change this setting only after consultation with
Delta customer service.
Overview
To change this setting, you need a special
password provided by Delta customer service.
You can find the contact information on the back
of this document.
This function allows you to reset the inverter to the factory set-
tings.
Setting options
Parameter Description Setting range
Return to Factory
Reset the inverter to the factory settings. None
Menu item path
Main Menu > Install Settings > Return to Factory
Loading the factory settings
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1. If the default information is displayed, press any button to open the main menu.
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed.
Inverter Info.
General Settings
Install Settings
2. Use the and buttons to select the Install Settings entry and then press the
ENT
button.
Password 0 * * *
energy production.
Adj. would affect
Warning:
3. Enter the password provided by Delta customer service.
Use the
and buttons to set the individual numerals.
Press the
ENT
button to confirm a number.
AC Connection: 3P3W
EPO: Normal Close
Anti-islanding: ON
Max. Power: 100%
Return to Factory
4. Use the and buttons to select the Return to Factory entry and then press the
ENT
button.
Return to factory?
Yes / No
5. Use the and buttons to select the Yes entry and then press the
ENT
button.