Installation and Operation Manual for Inverter RPI M50A_12s V1 EU EN 2017-03-09
8 Settings
8.5.5 Cos phi (P) (regulate cos phi via active
power)
These parameters are set according to the
requirements of the selected country. Changing
these parameter settings can invalidate the type
approval of the unit. Change this setting only after
consultation with Delta customer service.
Overview
Thisfunctionallowsyoutoregulatecosphi(cosφ)viathevia
active power.
0.8
0.8
1.0
100%
P/P
n
cos φ
Upper
limit
Lower
limit
Lower
limit
Upper
limit
Setting options
Parameter Description Setting range
Mode
Switch the function on and off.
ON|OFF
Q upper The upper limit of cosphi(cosφ).
0.80 .. 0.99 cap
1
0.80 .. 0.99 ind
P lower
The lower limit of the active power.
0 .. 100%
Q lower The lower limit of cosphi(cosφ).
0.80 .. 0.99 cap
1
0.80 .. 0.99 ind
P upper
The upper limit of the active power.
0 .. 100%
V lock-in 230.0 .. 253.0 V
V lock-out 207.0 .. 230.0 V
Menu item path
Main Menu > Active/Reactive Pwr > Reactive Power Ctrl
> Cos phi (P)
Calling up the menu item
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1. If the default information is displayed, press any button to open the main menu.
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed.

Table of Contents

Other manuals for Delta RPI M50A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta RPI M50A and is the answer not in the manual?

Delta RPI M50A Specifications

General IconGeneral
BrandDelta
ModelRPI M50A
CategoryInverter
LanguageEnglish

Related product manuals