Appendix B Accessories|VFD-B-P Series
B-24 Revision April 2009, SW V1.00
2. Connect Externally with the Encoder of 12V Power Supply and Output Signals to
Additional Tachometer
Connection between PG- 03 and the Encoder
Non-Fuse Breaker
NFB
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
M
3~
Motor
A
B
12V
0V
PG-03
A
B
OC
TP
A/O
B/O
RPM Meter
*Specification of the
Encoder is of 12V/OC output,
which could als o connec t
exter nally with the RPM wire
*Power of the should
be supplied by the customers
RPM meter
0V
A
B
A
B
PG
Shield
Te rm i na l
R/L1
S/L2
T/L3
Main circuit (power) terminals
Control circuit terminals
VFD-B-P
GND
5V
5V
0V
DC power
B.3.2.3 PG-03 Terminal Descriptions
1. Terminals
Terminal Symbols Descriptions
+12V
Power Supply of the Encoder: +12V
Output Voltage: +12V±5% 200mA
0V
Common point for the power supply and the signal
A-
,B-
B
Input signal from Pulse Generator. Input type is selected by FSW2. It
can be 1-phase or 2-phase input. Maximum 500kP/sec (z-phase
function is reserved). If the voltage exceeds 12V, it needs to use TP
type with connecting the external current limiting resistor(R). The
current should be within 5 to 15mA.
The formal of current limiting resistor is:
mA
R
VVin
mA 15
600
2
5 ≤
+Ω
≤
A/O, B/O
The Encoder signal output
Maximum: DC24V 300mA
Common point for signal grounding
2. Wiring Notes