EasyManuals Logo

Delta VFD-EL-W Series User Manual

Delta VFD-EL-W Series
217 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #152 background imageLoading...
Page #152 background image
Chapter 4 ParametersVFD-EL-W
147
In the flow control occasions such as constant pressure water pumps using PID control, set
Pr.00.03 = 3 and Pr.00.04 = 8. When the drive reboots after powered off, the start-up screen
displays 00:00 (as shown in the figure above). The displayed value on the left of “:” is the
physical quantity of PID target value; on the right of “:” shows the sensor output value (010V/
4–20 mA) corresponding to the actual physical quantity.
Refer to Pr.10.00 to set the target value; and Pr.10.18 to set the feedback value.
If the set and displayed target value directly correspond to physical quantities such as pressure,
temperature, flow, etc., you also need to set Pr.00.13 and Pr.00.14 at the same time.
00.13
User-defined Value
Default: 0
Settings
0–9999
Corresponds to the maximum operation frequency (Pr.01.00)
When Pr.00.13 is not set to zero, “Fautomatically disappears in the frequency setting page, and
the displayed last digit blinks. The Up/down key, multi-step speed and JOG function on the
keypad all changes ranges according to Pr.00.13.
When Pr.00.13 is not set to zero, and the frequency source is communication, use Pr.02.18 to
change the frequency command instead of using communication address 2001H.
00.14
Decimal Places for User-Defined Value
Default: 0
Settings
0–3
Sets the digital places for Pr.00.13.
For example: if the corresponding physical quantity such as pressure is to be set as 10.0 bar,
you need to set Pr.00.13 to 100, and set Pr.00.14 to 1. Pressure conversion relation: 0.1 Mpa =
1 bar = 1 kgf-cm
2
10.00
PID Set Point Selection
Default: 0
Settings
0: PID function disabled
1: Digital keypad
2: Reserved
3: Reserved
4: Set by Pr.10.11
Set Pr.00.03 = 3 and 00.04 = 8 for feedback value to display the PID set point on the control
panel at the same time.
When Pr.10.00 is set to 1 and operated by the keypad, adjust the set point by pressing the
up/down keys directly on any display interface if you need to set the set point.
When Pr.10.00 is set to 4, the setting range of Pr.10.11 is limited by the maximum operating
frequency of Pr.01.00. The maximum frequency value of 01.00 is the maximum value of the
physical quantity to the set point corresponds to the maximum range of the physical quantity
measured by the sensor (set in Pr.10.18).
If the set and displayed target value directly correspond to physical quantities such as pressure,

Other manuals for Delta VFD-EL-W Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD-EL-W Series and is the answer not in the manual?

Delta VFD-EL-W Series Specifications

General IconGeneral
BrandDelta
ModelVFD-EL-W Series
CategoryDC Drives
LanguageEnglish

Related product manuals