Chapter 4 ParametersVFD-EL-W
85
Pr.02.07 = 0: Use the Up/ Down keys on the digital keypad to increase or decrease the
frequency command.
Pr.02.07 = 1: The increasing or decreasing Frequency command (F) operates according to the
setting for acceleration or deceleration time, only valid during operation.
Pr.02.07 = 2: Increase and decrease the frequency command according to the setting for
Pr.02.08.
Pr.02.07 = 3: Increase and decrease the frequency command according to the setting for
Pr.02.08 (unit: pulse input). Every ON after OFF is regarded as one input pulse.
02.11
Keypad Frequency Command
Default: 60.00
Settings
0.00400.0 Hz
Sets the frequency command or reads the keypad frequency command.
02.12
Communication Frequency Command
Default: 60.00
Settings
0.00–400.00 Hz
Sets the frequency command or reads the communication frequency command.
02.13
Frequency Command Saving Mode
Default: 0
Settings
0: Save the frequency before power-off
1: Only save the keypad frequency command before power-off
2: Only save the communication frequency command before power-off
Determines whether to save the set frequency before power-off.
02.14
Initial Frequency Command Mode at Stop
Default: 0
Settings
0: Use current Frequency command
1: Use zero Frequency command
2: Refer to Pr.02.15 to set up
02.15
Initial Frequency Command Setting at Stop
Default: 60.00
Settings
0.00400.0 Hz
Pr.02.14 and Pr.02.15 determine the initial frequency command at STOP.
Pr.02.14 = 0: Sets the initial frequency command as current frequency command at STOP.
Pr.02.14 = 1: The initial frequency command returns to zero at STOP.
Pr.02.14 = 2: The initial frequency command operates according the setting for Pr.02.15 at
STOP.