Modbus Offset Register
Description
* System=sum of three phases
resettable)
46010 6009 Positive kVAR System System Net Instantaneous Positive Reactive Power
(kVAR) (net sum of all individual kVARs, if sum is
negative value=0)
46011 6010 kVAh System LSW System Apparent Energy, LSW (resettable)
46012 6011 kVAh System MSW System Apparent Energy, MSW (resettable)
46013 6012 kVA System System Instantaneous Apparent Power
46014 6013 Positive Displacement PF
System
System Positive Displacement Power Factor (dPF);
Register is 100x actual value (If the System dPF
(44014) is positive, this register will contain that value
else it will be zero)
46015 6014 Positive Apparent PF System System Positive Apparent Power Factor (aPF);
Register is 100x actual value (If the System aPF
(44015) is positive, this register will contain that value
else it will be zero)
46016 6015 Amps System Avg Average of the current in all phases.
46017 6016 Volts Line to Line Avg Average of the system line to line voltages.
46018 6017 Volts Line to Neutral Avg Average of the system line to neutral voltages.
46019 6018 Volts L1 to L2 Individual phase to phase voltages.
46020 6019 Volts L2 to L3
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DENT Instruments powerscout 3037 and is the answer not in the manual?

DENT Instruments powerscout 3037 Specifications

General IconGeneral
BrandDENT Instruments
Modelpowerscout 3037
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals