68
Modbus Offset Register
Description
* System=sum of three phases
46021 6020 Volts L3 to L1 “
46022 6021 Measured Line Frequency Line frequency x 10 (e.g., 602 = 60.2 Hz). On startup,
20 point averaging array is filled with first frequency
read.
46023 6022 Positive kWh L1 LSW Individual Phase Positive True Energy LSW (kWh,
resettable)
46024 6023 Positive kWh L1 MSW Individual Phase Positive True Energy MSW (kWh,
resettable)
46025 6024 Positive kWh L2 LSW “
46026 6025 Positive kWh L2 MSW “
46027 6026 Positive kWh L3 LSW “
46028 6027 Positive kWh L3 MSW “
46029 6028 Positive kW L1 Individual Phase Instantaneous Positive True Powers
(kW)
46030 6029 Positive kW L2 “
46031 6030 Positive kW L3 “
46032 6031 Positive kVARh L1 LSW Individual Phase Positive Reactive Energy LSW
(kVARh, resettable)
46033 6032 Positive kVARh L1 MSW Individual Phase Positive Reactive Energy MSW
(kVARh, resettable)
46034 6033 Positive kVARh L2 LSW “
46035 6034 Positive kVARh L2 MSW “
46036 6035 Positive kVARh L3 LSW “
46037 6036 Positive kVARh L3 MSW “
46038 6037 Positive kVAR L1 Individual Phase Positive Instantaneous Reactive
Powers (kVAR)