69
Modbus Offset Register
Description
* System=sum of three phases
46039 6038 Positive kVAR L2
46040 6039 Positive kVAR L3
46041 6040 kVAh L1 LSW Individual Phase Apparent Energy LSW (kVAh,
resettable)
46042 6041 kVAh L1 MSW Individual Phase Apparent Energy MSW (kVAh,
resettable)
46043 6042 kVAh L2 LSW
46044 6043 kVAh L2 MSW
46045 6044 kVAh L3 LSW
46046 6045 kVAh L3 MSW
46047 6046 kVA L1 Individual Phase Instantaneous Apparent Powers
(kVA)
46048 6047 kVA L2
46049 6048 kVA L3
46050 6049 Positive Displacement PF L1 Individual Phase Positive Displacement Power Factors
(dPF); Register is 100x actual value (If the Individual
dPF (44050) is positive, this register will contain that
value else it will be zero)
46051 6050 Positive Displacement PF L2
46052 6051 Positive Displacement PF L3
46053 6052 Positive Apparent PF L1 Individual Phase Positive Apparent Power Factors
(aPF); Register is 100x actual value (If the Individual
aPF(44053) is positive, this register will contain that
value else it will be zero)
46054 6053 Positive Apparent PF L2
46055 6054 Positive Apparent PF L3
46056 6055 Amps L1 Individual Phase Instantaneous Currents (A)
46057 6056 Amps L2