71
Modbus Offset Register
Detailed Description
* System=sum of three phases
47004 7003 kW Demand System Max System Maximum Demand (peak demand).
47005 7004 kW Demand System Now Average Power (kW) for most recent demand window
47006 7005 Negative kW System Max System Net Highest Instantaneous Negative Draw
Since Reset (kW, resettable)
47007 7006 Negative kW System Min System Net Lowest Instantaneous Negative Draw
Since Reset (kW, resettable)
47008 7007 Negative kVARh System LSW System Net Negative Reactive Energy LSW (kVARh,
resettable)
47009 7008 Negative kVARh System MSW System Net Negative Reactive Energy MSW (kVARh,
resettable)
47010 7009 Negative kVAR System System Net Instantaneous Negative Reactive Power
(kVAR) (net sum of all individual kVARs, if sum is
positive value=0)
47011 7010 kVAh System LSW System Apparent Energy LSW (kVAh, resettable)
47012 7011 kVAh System MSW System Apparent Energy MSW (kVAh, resettable)
47013 7012 kVA System System Instantaneous Apparent Power (kVA)
47014 7013 Negative Displacement PF
System
System Negative Displacement Power Factor (dPF);
Register is 100x actual value (If the System dPF
(44014) is Negative, this register will contain that
value else it will be zero)
47015 7014 Negative Apparent PF System System Negative Apparent Power Factor (aPF);
Register is 100x actual value (If the System aPF
(44015) is Negative, this register will contain that
value else it will be zero)
47016 7015 Amps System Avg Average of the current in all phases.