Modbus Offset Register
Detailed Description
* System=sum of three phases
47017 7016 Volts Line to Line Avg Average of the system line to line voltages.
47018 7017 Volts Line to Neutral Avg Average of the system line to neutral voltages.
47019 7018 Volts L1 to L2 Individual phase to phase voltages.
47020 7019 Volts L2 to L3
47021 7020 Volts L3 to L1
47022 7021 Measured Line Frequency Line frequency x 10 (e.g., 602 = 60.2 Hz). On startup,
20 point averaging array is filled with first frequency
read.
47023 7022 Negative kWh L1 LSW Individual Phase Negative True Energy LSW (kWh,
resettable)
47024 7023 Negative kWh L1 MSW Individual Phase Negative True Energy MSW (kWh,
resettable)
47025 7024 Negative kWh L2 LSW
47026 7025 Negative kWh L2 MSW
47027 7026 Negative kWh L3 LSW
47028 7027 Negative kWh L3 MSW
47029 7028 Negative kW L1 Individual Phase Instantaneous Negative True Powers
(kW)
47030 7029 Negative kW L2
47031 7030 Negative kW L3
47032 7031 Negative kVARh L1 LSW Individual Phase Negative Reactive Energy LSW
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DENT Instruments powerscout 3037 and is the answer not in the manual?

DENT Instruments powerscout 3037 Specifications

General IconGeneral
BrandDENT Instruments
Modelpowerscout 3037
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals