72
Modbus Offset Register
Detailed Description
* System=sum of three phases
47017 7016 Volts Line to Line Avg Average of the system line to line voltages.
47018 7017 Volts Line to Neutral Avg Average of the system line to neutral voltages.
47019 7018 Volts L1 to L2 Individual phase to phase voltages.
47020 7019 Volts L2 to L3 “
47021 7020 Volts L3 to L1 “
47022 7021 Measured Line Frequency Line frequency x 10 (e.g., 602 = 60.2 Hz). On startup,
20 point averaging array is filled with first frequency
read.
47023 7022 Negative kWh L1 LSW Individual Phase Negative True Energy LSW (kWh,
resettable)
47024 7023 Negative kWh L1 MSW Individual Phase Negative True Energy MSW (kWh,
resettable)
47025 7024 Negative kWh L2 LSW “
47026 7025 Negative kWh L2 MSW “
47027 7026 Negative kWh L3 LSW “
47028 7027 Negative kWh L3 MSW “
47029 7028 Negative kW L1 Individual Phase Instantaneous Negative True Powers
(kW)
47030 7029 Negative kW L2 “
47031 7030 Negative kW L3 “
47032 7031 Negative kVARh L1 LSW Individual Phase Negative Reactive Energy LSW