73
Modbus Offset Register
Detailed Description
* System=sum of three phases
(kVARh, resettable)
47033 7032 Negative kVARh L1 MSW Individual Phase Negative Reactive Energy MSW
(kVARh, resettable)
47034 7033 Negative kVARh L2 LSW
47035 7034 Negative kVARh L2 MSW
47036 7035 Negative kVARh L3 LSW
47037 7036 Negative kVARh L3 MSW
47038 7037 Negative kVAR L1 Individual Phase Negative Instantaneous Reactive
Powers (kVAR)
47039 7038 Negative kVAR L2
47040 7039 Negative kVAR L3
47041 7040 kVAh L1 LSW Individual Phase Apparent Energy LSW (kVAh,
resettable)
47042 7041 kVAh L1 MSW Individual Phase Apparent Energy MSW (kVAh,
resettable)
47043 7042 kVAh L2 LSW
47044 7043 kVAh L2 MSW
47045 7044 kVAh L3 LSW
47046 7045 kVAh L3 MSW
47047 7046 kVA L1 Individual Phase Instantaneous Apparent Powers
(kVA)
47048 7047 kVA L2
47049 7048 kVA L3
47050 7049 Negative Displacement PF L1 Individual Phase Negative Displacement Power
Factors (dPF); Register is 100x actual value (If the
Individual dPF(44050) is Negative, this register will
contain that value else it will be zero)
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DENT Instruments powerscout 3037 and is the answer not in the manual?

DENT Instruments powerscout 3037 Specifications

General IconGeneral
BrandDENT Instruments
Modelpowerscout 3037
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals